8 - CONTROL
ALARMS - Tab 1
Code Short description description
AA003 Fire Units on alert for fire alarm in progress
aa004 DirtyFilter Air dirty filter
eE001 Phase monitor Fault on the network power supply
EE002 Opening Vain Access compartments open
EE005 Electrical Filter Electrical Filter fault
ee006 PlantConfig Absence of a configuration of the type of unit operation upon starting
eE007 SupplyFan Intervention of the protections of air supply fan
eE009 Exhaust Fan Intervention of the protections of return / exaust fan
EE010 High Temp. Integration Protection of maximum temperature on the auxiliary heater
EE011 Ovl Integration Intervention of the protection of the auxiliary heater
ee020 Offline thermostat. User POL822 interface module not responding
ee027 ReturnTemp Return temperature probe fault
ee028 SupplyTemp Supply temperature probe fault
ee029 AirExtTemp External air temperature probe fault
ee030 RHSupply Supply RH probe fault
ee031 RHReturn Return RH probe fault
ee032 RHOutdoor Outdoor air RH probe fault
ee033 QualityAir Room air quality probe fault
ee035 SupplyPDiff Differential pressure trasducer supply fan fault
ee037 ExhaustPDiff Differential pressure trasducer exaust fan fault
ee039 PSupply Pressure trasducer suply fan fault
ee044 Humidifier alarm Humidifier board disconnected
ee050 H2O plant temp Plant water temperature probe fault
ee051 H2O freeze temp Heating water coil temperature probe fault
ee052 Recover temp Recovery temperature probe fault
ee059 PostRiscMod HwError Post-heating control board fault
ee060 PostRiscMod BlkError Post-heating control board fault
ee061 PostRiscMod FailSaveState Post-heating control board fault
ee062 PostRiscMod UpsNotAv Post-heating UPS board fault
ee063 PostRiscMod PBTime Post-heating control board not responding
ee064 Pump recover Recovery pump fault
ee065 PostRiscMod HW-FailSaveState Post-heating control board fault
ee068 ExhaustPDiff 2nd Differential pressure trasducer exaust 2nd fan fault
ee069 Exhaust Fan 2nd Intervention of the protections of return / exaust 2nd fan
ee090 SafeMode SafeMode
Alarms encoding
Code Type Reset
eE Electrical From Auto to Man
EE Electrical Manual
ee Electrical Automatic
iI Hydraulics From Auto to Man
II Hydraulics Manual
ii Hydraulics Automatic
Alarms encoding
Code Type Reset
fF refr. circuit From Auto to Man
FF refr. circuit Manual
ff refr. circuit Automatic
aA Air From Auto to Man
AA Air Manual
aa Air Automatic
From Auto to Man: automatic reset , after N alarm → manual reset