Mode button. Use this button to call mode change.*
9
Fault reset button. Use this button to acknowledge alarms
and deactivate the horn output. Inactive alarms will disappear
immediately and status of active alarms will be changed to
“confirmed” so they will disappear as soon as their reasons
GCB button. Works in MAN mode only. Press this button to
open or close the GCB manually. Note that certain conditions
must be valid otherwise GCB closing is blocked.*
MCB button. Works in MAN mode only. Press this button to
open or close the MCB manually.*
CAUTION!
You can disconnect the load from the mains supply with this
button! Be sure you know well what you are about to do!
Colour display, 800x600 pixels.
* - It is valid in default SPtM configuration only. Screens description and buttons from
8 to 13 could have different meaning in customized versions or SW branches.
INTELIVISION 8 LED INDICATION
POWER indication. LED diode turns on when InteliVision 8 is
powered up.
Alarm LED indication indicate alarms. Yellow
colour for the first level alarms and red colour for the second level
alarms.
Hint:
LED diode blink when at least one acknowledge alarm is present in
the Alarm List.
LED diode lights when alarms were acknowledged but are still
indication. Engine LED indication lights only when engine is
running.
Hint:
When you switch on InteliVision 8 display, Power LED turns on and Engine and
Alarm LEDs start to blink for a while.
InteliVision 5, InteliVision 8 – Operator guide, ©ComAp – January 2014
IGS-NT Operator Guide 01-2014.pdf
23