Load reconnection – automatic -> AutoLd recon = ENABLED
Ld recon del Ld recon delLd recon del
BO Load shed 2
Ld recon level
Gen-set power
BO Load shed 3
BO Load shed 1
opened
opened
opened
Load reconnection – manual -> AutoLd recon = DISABLED
Power derating
This function linearly decreases genset nominal power according to analog input value.
Gen-set power starts decreasing when temperature measured by Analog input Power deratingX exceeds
DeratingX strt value.
Gen-set power is at DeratedX pwr value when temperature measured by Analog input PowerDeratingX is
equal or higher than DeratingX end value.
Hint:
To use Power derating function configure at first Analog input PowerDeratingX to any IS-NT or IS-AIN
analog input terminal by GenConfig.