Control Specification SiUS121632EA
96 Functions and Control
4.14 Malfunctions
4.14.1 Sensor Malfunction Detection
Sensor malfunction may occur either in the thermistor or current transformer (CT) system.
Relating to Thermistor Malfunction
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Gas pipe thermistor
5. Outdoor temperature thermistor
6. Liquid pipe thermistor
Relating to CT Malfunction
Refer to CT or related abnormality on page 182 for details.
4.14.2 Detection of Overcurrent and Overload
Outline In order to protect the inverter, an excessive output current is detected and the OL temperature is
observed to protect the compressor.
Details
If the inverter current exceeds 15.5 ~ 18.5 A (depending on the model), the system shuts down
the compressor.
If the OL (compressor head) temperature exceeds 130°C (266°F), the compressor stops.
4.14.3 Refrigerant Shortage Control
Outline Detection by power consumption
Refrigerant shortage is detected if the power consumption is below the specified value and the
frequency is higher than the specified frequency.
When refrigerant is insufficient, the power consumption is lower than normal operation. Hence
refrigerant shortage is detected by checking power consumption.
Refer to refrigerant shortage on page 160 for details.
4.14.4 Anti-icing Function
During cooling, if the indoor heat exchanger temperature in the operation stopped room drops
below the specified temperature for a specified time, the electronic expansion valve is opened in
the operation stopped room as specified, and the fully closed operation is carried out. After this, if
freezing abnormality occurs longer than a specified time, the system is shut down.
Frequency
Refrigerant shortage zone
(R23015)
40 Hz
Power consumption
(Input current)

Table of Contents

Other manuals for Daikin 2MXL18QMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXL18QMVJU and is the answer not in the manual?

Daikin 2MXL18QMVJU Specifications

General IconGeneral
BrandDaikin
Model2MXL18QMVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals