SiUS121632EA Control Specification
Functions and Control 85
4.4.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not used when defrosting.)
4.5 Discharge Pipe Temperature Control
Outline The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Details
All outdoor units
A (Hz) 26
B (Hz) 48
C (Hz) 70
D (seconds) 120
E (seconds) 500
F (seconds) 180
A
DEF
B
C
(R13528)
(Hz)
Frequency
(sec.)
Time
Zone Control
Stop zone When the temperature reaches the stop zone, the compressor stops.
Dropping zone The upper limit of frequency decreases.
Keep zone The upper limit of frequency is kept.
Reset zone The upper limit of frequency is canceled.
All outdoor units
120˚C (248˚F)
111˚C (231.8˚F)
109˚C (228.2˚F)
107˚C (224.6˚F)
107˚C (224.6˚F)
A
B
C
D
E
Reset zone
Stop zone
Dropping
zone
Keep
zone
(R14266)
A
C
D
E
B
Discharge pipe
temperature

Table of Contents

Other manuals for Daikin 2MXL18QMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXL18QMVJU and is the answer not in the manual?

Daikin 2MXL18QMVJU Specifications

General IconGeneral
BrandDaikin
Model2MXL18QMVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals