Troubleshooting for Outdoor Unit SiUS121632EA
160 Service Diagnosis
7. Troubleshooting for Outdoor Unit
7.1 Refrigerant Shortage
Error Code
U0
Outdoor Unit LED
Display
A
j
1
h
2
h
3
i
4
i
5
h
Method of Error
Detection
Refrigerant shortage is detected by checking the input current value and the compressor running
frequency. If there is insufficient refrigerant, the input current tends to be lower than the normal
value.
Error Decision
Conditions
The following conditions continue for 7 minutes.
Input current
A × output frequency + B
Output frequency > C
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor,
room or outdoor temperature thermistor
Closed stop valve
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Defective electronic expansion valve
A
(–)
B (A) C (Hz)
27/1000 2 40

Table of Contents

Other manuals for Daikin 2MXL18QMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXL18QMVJU and is the answer not in the manual?

Daikin 2MXL18QMVJU Specifications

General IconGeneral
BrandDaikin
Model2MXL18QMVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals