SiUS121632EA Troubleshooting for Outdoor Unit
Service Diagnosis 163
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB (main PCB).
Check for such factors for a
long term.
(R22370)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
NO
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
Disturbance factors
Noise
Power supply distortion
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Replace the indoor
unit PCB (control PCB).
Turn on
the power. System
restarted? (Repeat a few
times.)
Error
again within 3 minutes
after turning on the
power?
Loose or
disconnected?
NO
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Does the
outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?

Table of Contents

Other manuals for Daikin 2MXL18QMVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXL18QMVJU and is the answer not in the manual?

Daikin 2MXL18QMVJU Specifications

General IconGeneral
BrandDaikin
Model2MXL18QMVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals