Graph 3 External signal 4-20mA vs Active Setpoint - Cooling mode(left)/ Heating mode(right)
4.10.2.3 Setpoint Reset by DT
When the DT is selected as Setpoint Reset option, the LWT active setpoint(AS) is calculated applying a correction based
on the temperature difference ΔT between the leaving water temperature(LWT) and the evaporator entering(returning)
water temperature (EWT). When the |ΔT| becomes smaller than the Start Reset ΔT setpoint(SRΔT), the LWT active
setpoint is proportionally increased (if Cooling mode set) or decreased (if Heating mode is set) of a maximum value equal
to the Max Reset(MR) parameter.
Max Reset setpoint. It represents the maximum temperature
variation that the selection of the 4-20mA option can cause on the
LWT.