1-3
1.2 Protection Device and Setting Value
Component Name
Detector Symbol
Setting Value Alarm
High pressure switch HPS
OFF2400kPa24.47kg/cm
2
ON1900kPa19.37kg/cm
2
E101
F101
Pressure relief valve PRV Open2450kPa25.0kg/cm
2
)−
Fusible plug 95100℃(203212℉)
Built-in thermal protector
for condenser fan motor
Q1M
OFF135℃±5℃(275℉±41℉)
ON86℃±15℃(187℉±59℉)
Built-in thermal protector
for evaporator fan motor
OFF145℃±5℃(293℉±41℉)
ON94℃±15℃(201℉±59℉)
Circuit breaker (ELCB) CB 30A100mA)−
Fuse and Protection Circuit
Board Fuse Type Protection Circuit Alarm
I/O board
EC2
F1U
F10A 250V
fast-acting type
I/O board control powerDC13.5V, 5V, 3.3V
F2U
PCC1, PCC2, CFH, CFL, EFH, EFL
HSV, RSV, LSV, ESV
F703
F707
E115
E117
F3U Spare
PT/CT
board
EC7
F11U 8A 600V PT/CT board control power
Noise filter
board
EC9
F5U
12.5A 300A
Surge absorber 1 (lightning surge protection)
<Non-replaceable>
F6U
Surge absorber 2 (lightning surge protection)
<Non-replaceable>
F7U
Surge absorber 3 (lightning surge protection)
<Non-replaceable>
F8U 8A 600V Inverter control circuit <Non-replaceable>
I/O board
EC2
TH3
2.5A 72V
Automatic reset
RM (Remote Monitoring) circuit
<Non-replaceable>
TH2 TransFresh circuit <Non-replaceable>
01章LX10F11B3TR16-02En.indd1-301章LX10F11B3TR16-02En.indd1-3 2016/02/029:09:322016/02/029:09:32
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B3 and is the answer not in the manual?

Daikin LX10F11B3 Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B3
CategoryInverter
LanguageEnglish

Related product manuals