4-24
4.9 Emergency Operation at
Controller Malfunction
Manually change
Following manually changing are required for emergency
operation in the case of controller malfunction.
(1) Wiring change of controller
Change wiring to operate compressor, EFM and
CFM.
Refer the details to paragraph 4.9.1.
Preparation parts: Shot circuit connector (fitted
inside of controller)
(2) Fix the opening of EEV, EMV and DMV
Refer the details to paragraph 4.9.2 to 4.9.4.
Preparation parts: Emergency magnet (Parts
No. 1896110)
Note: Fixing of opening for EEV, EMV or DMV is
applicable for emergency use when controller
is normal and EEV, EMV or DMV coil is
malfunction.
Operation condition at emergency operation
Temperature can not be controlled. Turn the
circuit breaker ON or OFF to maintain the target
temperature manually.
Operation Mode
Operation Condition
Cooling operation
in frozen mode
Compressor: Continuous running
with fixed speed.
EFM : Low Speed
CFM : High Speed
EEV, EMV, DMV: Fixed opening
LSV : Open
Heating operation
EFM : High Speed
4.9.1 Wiring Change of Controller
Preparation Turn circuit breaker OFF.
Disconnect power connector X24A Black
located on I/O board. (To de-energized to CPU
board.)
Refer location of X24A to I/O board in
paragraph 1.3.4.
Remove short-circuit connectors fitted inside
controller box. (Right figure)
SCC2-2 (Red)
For heating
SCC2-1 (Blue)
For cooling
SCC1-1 (White)
For positive phase
SCC1-2 (Yellow)
For reverse phase
Connect SCC1-1White to X31A located
on I/O board and SCC2-1Blue to X32A for
<Cooling>.
Check the insertion direction of the connector.
DER ]TAEH[
EULB ]LOOC[
A13X
A23X
PCC1
PCC2
A13X
EMERGENCY
I/O board
SCC1-1(White)
SCC2-1 (Blue)
For cooling
Confirmation
of power
phase
Turn circuit breaker ON.
If the power supply is in reversed phase,
condenser fan turns reverse.
In the case of reversed phase, turn circuit
breaker OFF and replace SCC1-1 (White) to
SCC1-2 (Yellow).
A13X
A23X
DER ]TAEH[
EULB ]LOOC[
PCC1
PCC2
A13X
EMERGENCY
SCC1-2 (Yellow)
Forcible
operation of
Compressor,
EFM and CFM
Cooling Operation
Keep cooling operation as it is.
A13X
A23X
DER ]TAEH[
EULB ]LOOC[
PCC1
PCC2
A13X
EMERGENCY
SCC2-1 (Blue)
For cooling
Heating Operation
1. Turn circuit breaker OFF.
2. Replace SCC2-1 (Blue) to SCC2-2Red
for <Heating>.
3. Turn circuit breaker ON.
A13X
A23X
DER ]TAEH[
EULB ]LOOC[
PCC1
PCC2
A13X
EMERGENCY
SCC2-2 (Red)
For heating
Caution Recheck power supply phase when you operate again after the power is turned OFF.
04章LX10F11B3TR16-02En.indd4-2404章LX10F11B3TR16-02En.indd4-24 2016/02/0316:22:152016/02/0316:22:15
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B3 and is the answer not in the manual?

Daikin LX10F11B3 Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B3
CategoryInverter
LanguageEnglish

Related product manuals