5-7
5.6 Parts Replacement
5.6.1 Cooling Water Pressure Switch
(WPS)
Type LCB-MB10
Setpoint OFF 98kPa (1.0kg/cm
2
)
ON 39kPa (0.4kg/cm
2
)
This is used to switch between air-cooled
operation and water-cooled operation. The
cooling water flows, and when the inlet water
pressure reaches the setpoint, the contact
switches OFF, the condenser fan is stopped, and
water-cooled operation is performed.
(1) Replacement procedure
Remove the WPS lead wire from the controller
terminal block.
Stop the cooling water pump, check that no
water pressure is being applied, and then
remove the WPS.
Replace the WPS, apply seal tape around the
threads, and then tighten the screw.
Cooling Water Pressure Switch (WPS)
Cooling water inlet joint
Cooling water outlet joint
Inlet joint cap
Outlet joint cap