EasyManuals Logo
Home>Daikin>Inverter>LX10F11B3

Daikin LX10F11B3 User Manual

Daikin LX10F11B3
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #54 background imageLoading...
Page #54 background image
2-25
004 F401 F405 F407 F409
Alarm
Logic
and
Possible
Causes
F401 SS, DSS, RS and DRS all failed during chilled mode, or X16A (CPU board) is disconnected.
F405 Multiple sensor (HPT,DCHS1,DCHS2) all failure.
F407 Multiple sensor (HPT,LPT) all failure.
F409 Multiple sensor (LPT,DCHS1,DCHS2) all failure.
Trouble
Shooting
The unit cannot perform backup operation and cannot be controlled.
Replace each failed sensor.
Refer to
016
,
017
, and
019
.
Controller
Action
F401, F405, F407, F409Unit stop
005 F701 E701
Alarm
Logic
The power supply voltage is AC565V or AC329V.
Possible
Causes
The power supply voltage is high ( AC565V) or low ( AC329V).
Trouble
Shooting
Check if the actual power supply within range (AC329VAC565V).
Controller
Action
F701Unit stop
E701 Restart after 3 minutes
02章19-44LX10F11B3TR16-02En.indd2-2502章19-44LX10F11B3TR16-02En.indd2-25 2016/02/0217:17:372016/02/0217:17:37
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B3 and is the answer not in the manual?

Daikin LX10F11B3 Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B3
CategoryInverter
LanguageEnglish

Related product manuals