3-7
P08
INV
check
T081
The frequency does not
match to command frequency.
T082
No pressure difference
between high and low pressure.
P10
EMV, ESV
check
T101 EMV or ESV failure
EMV wiring failure
Check EMV coil and wiring.
EMV coil burning out
Check EMV outlet pipe temperature.
ESV coil failure
Check ESV coil and wiring.
ESV valve body failure
Check ESV outlet pipe temperature.
T102 ESV failure
ESV wiring failure
Check ESV coil and wiring.
ESV coil burning out
Check clicking sound from ESV.
T103 EMV failure
EMV wiring failure
Check EMV coil and wiring.
EMV coil burning out
Check EMV outlet pipe temperature.
P12
LSV
check
T121
LSV does not operate.
LSV coil failure
Check LSV coil and wiring.
LSV valve body failure
Check LSV outlet pipe temperature.
P14
HSV
check
T141 HSV does not open.
HSV coil failure
Check HSV coil and wiring
HSV valve body failure
Check HSV outlet pipe temperature.
P16
RSV
check
T161 RSV does not open.
RSV coil failure
Check RSV coil and wiring.
RSV valve body failure
Check RSV outlet pipe temperature.
P18
DMV
check
T181
DMV does not operate.
DMV wiring failure
Check DMV coil and wiring.
DMV coil burning out
Check clicking sound from DMV.
P20
HPS
check
T201 OFF value is low.
HPS failure
HPT failure
Gas leakage from
manifold gauges
Check HPT.
Compare to manifold
gauges.
Remove manifold
gauges.
T202 Does not reset
T203
HPS: High pressure
does not rise.
HPS does not operate.
T204
HPS: High pressure
does not drop.
P22
Pump down
check
T221
Pump down time is
too long.
EEV failure
Check EEV coil, wiring, valve body.
Leakage through HSV
Check HSV outlet pipe temperature.
Leakage through RSV
Check RSV outlet pipe temperature.
Leakage through ESV
Check ESV outlet pipe temperature.
P24
Valve leak
check
T241
Solenoid valve
internal leakage
Leakage through HSV
Check HSV outlet pipe temperature.
Leakage through RSV
Check RSV outlet pipe temperature.
Leakage through ESV
Check ESV outlet pipe temperature.
Leakage through EEV
Check EEV outlet pipe temperature.
P50
0
pull-down
T501
Ambient temperature
is out of condition.
(Unit is normal.)
Ambient temperature is
below -10 and above
43
Check ambient temperature
T502
Pull-down time is too long.
P60
0
maintenance
No alarm
No judgment
P70 Defrost test
T701
Defrost initiation
conditions out of range
EOS failure Check EOS.
HSV internal leakage
Check HSV outlet pipe temperature.
T702
Defrost time is too long.
EOS failure Check EOS.
P80
-18 pull-down
T801
Pull-down time is too long.
P90
-18
maintenance
No alarm
03章LX10F11B3TR16-02En.indd3-703章LX10F11B3TR16-02En.indd3-7 2015/12/2115:43:112015/12/2115:43:11
https://daikin-p.ru

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin LX10F11B3 and is the answer not in the manual?

Daikin LX10F11B3 Specifications

General IconGeneral
BrandDaikin
ModelLX10F11B3
CategoryInverter
LanguageEnglish

Related product manuals