user InTerfaCe
www.DaikinApplied.com 19 OM 1077-1 • MAVERICK I
General Information Screen
This is the home page of the system. At power up or after a
period of time of 5 minutes (display delay) without the selection
of any buttons, the system returns to this screen and resumes
scrolling through the items of this group.
The general information screen automatically scrolls through
the different menu items at 2-second intervals. When the user
presses any button, the changing of screens stops until the
display delay expires.
The software is programmed in the factory and cannot be
changed. The item “Alarms” is dependent upon the existence
of an alarm and it may display either “No Active Alarm” or
“Check Alarms!” Another screen outside this group shows the
details of existing alarms. The option for system conguration
is set with a conguration key from the factory.
Unit Status Screen
The status screen shows basic information about the operation
of the unit, such as mode of operation, inputs, outputs, and
capacity of cooling or heating.
Table 7: Unit Status Screen
Item Range
Mode
STANDBY
Fan Only
COOL STG1 ECON
COOL STG2 CC/ECO
COOL STG1 COMP
COOL STG2 COMP
HEAT STG1 COMP
HEAT STG2 COMP
HEAT STG1 ELEC
HEAT STG2 ELEC
HEAT STG1 GAS
HEAT STG2 GAS
HEAT STG2 CC/ELE
HEAT STG3 CC/ELE
HEAT STG4 CC/ELE
Defrost 1
Defrost 2
Inputs
24VAC Inputs
Y1 – ON/OFF
Y2 – ON/OFF
W1 – ON/OFF
W2 – ON/OFF
B – ON/OFF
G – ON/OFF
OCC – ON/OFF
LPS1 – ON/OFF
LPS2 – ON/OFF
HPS1 – ON/OFF
HPS2 – ON/OFF
CFS – ON/OFF
SMKS – ON/OFF
FPS – ON/OFF
Outputs
Compressor 1 – ON/OFF
Compressor 2 – ON/OFF
Rev Vlv 1 – ON/OFF
Rev Vlv 2 – ON/OFF
Heat 1 – ON/OFF
Heat 2 – ON/OFF
Outdr Fan 1 – ON/OFF
Outdr Fan 2 – ON/OFF
Indoor Fan – ON/OFF
Capacity Heating / Cooling – 100%