EasyManuals Logo
Home>Daikin>Air Conditioner>RXS09LVJU

Daikin RXS09LVJU Service Manual

Daikin RXS09LVJU
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #163 background imageLoading...
Page #163 background image
Check SiUS091133
153 Service Diagnosis
5.15 Power Module Check
Check No.22
Note: Check to make sure that the voltage between (+) and (–) of the power module is approx. 0 V before
checking.
Disconnect the compressor harness connector from the outdoor unit PCB. To disengage the
connector, press the protrusion on the connector.
Follow the procedure below to measure resistance between the terminals of the power module
and the terminals of the compressor with a multi-tester. Evaluate the measurement results
referring to the following table.
09/12 class
Negative (–) terminal of
tester (positive terminal
(+) for digital tester)
Power module
(+)
UVW Power module
(–)
UVW
Positive (+) terminal of
tester (negative terminal
(–) for digital tester)
UVW Power module
(+)
UVW Power module
(–)
Resistance is OK. several k ~ several M
Resistance is NG. 0 or
(R16069)
Power module

Table of Contents

Other manuals for Daikin RXS09LVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXS09LVJU and is the answer not in the manual?

Daikin RXS09LVJU Specifications

General IconGeneral
BrandDaikin
ModelRXS09LVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals