EasyManuals Logo
Home>Daikin>Air Conditioner>RXS09LVJU

Daikin RXS09LVJU Service Manual

Daikin RXS09LVJU
414 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #399 background imageLoading...
Page #399 background image
Field Settings SiUS091133
389 Trial Operation and Field Settings
4.4 Facility Setting Jumper and Switch (Cooling at Low
Outdoor Temperature)
Outline This function is limited only for facilities (the target of air conditioning is equipment such as
computer. Never use it in spaces occupied by humans such as a residence or office.
Detail You can expand the operation range to –10°C (14°F) by cutting the jumper or turning on switch on
the outdoor unit PCB. If the outdoor temperature falls to –18°C (–0.4°F) or lower, the operation
stops. If the outdoor temperature rises, the operation starts again.
09/12 class
15/18 class
1
2
3
S70
S40
S2
S90
J5
J4
J3
(R12187)
Cut the jumper J4.
J5
J7
J8
J6
GND
Top panel
PCB
1) Remove the
3 screws.
Drip proof
cover
2) Remove the
drip proof
cover.
3) Cut the
jumper J6.
(R16698)

Table of Contents

Other manuals for Daikin RXS09LVJU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin RXS09LVJU and is the answer not in the manual?

Daikin RXS09LVJU Specifications

General IconGeneral
BrandDaikin
ModelRXS09LVJU
CategoryAir Conditioner
LanguageEnglish

Related product manuals