20 | Configuration
Installer and user reference guide
138
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
E.g., when your system is operating in cooling, you do not need as much cooling
under low outdoor ambient temperatures (e.g., 25°C) as under high outdoor
ambient temperatures (e.g., 35°C). Using this idea, the system automatically starts
increasing its refrigerant temperature, automatically reducing the delivered
capacity and increasing the system's efficiency.
E.g., when your system is operating in heating, you do not need as much heating
under high outdoor ambient temperatures (e.g., 15°C) as under low outdoor
ambient temperatures (e.g., –5°C). Using this idea, the system automatically starts
decreasing its refrigerant temperature, automatically reducing the delivered
capacity and increasing the system's efficiency.
To activate this in… Change…
Cooling operation [2‑8]=0 (default)
Heating operation [2‑9]=0 (default)
Hi-sensible/economic (cooling/heating)
The refrigerant temperature is set higher/lower (cooling/heating) compared to
basic operation. The focus under high sensible mode is comfort feeling for the
customer.
The selection method of indoor units is important and has to be considered as the
available capacity is not the same as under basic operation.
For details concerning to Hi-sensible applications, please contact your dealer.
To activate this in… Change…
Cooling operation [2‑8] to the appropriate value, matching
the requirements of the pre-designed
system containing a high sensible
solution.
Heating operation [2‑9] to the appropriate value, matching
the requirements of the pre-designed
system containing a high sensible
solution.
[2‑8] T
e
target (°C)
3 7
4 8
5 9
6 10
7 11
[2‑9] T
c
target (°C)
1 41
3 43
20.3.2 Available comfort settings
For each of above modes a comfort level can be selected. The comfort level is
related to the timing and the effort (energy consumption) which is put in achieving
a certain room temperature by temporarily changing the refrigerant temperature
to different values in order to achieve requested conditions more quickly.

Table of Contents

Other manuals for Daikin VRV IV+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV+ and is the answer not in the manual?

Daikin VRV IV+ Specifications

General IconGeneral
TypeVRV (Variable Refrigerant Volume)
SeriesVRV IV+
RefrigerantR-410A
Energy EfficiencyHigh
Inverter TechnologyYes
Operating Temperature Range (Cooling)-5°C to 46°C
Cooling Capacity Range22.4 kW - 168 kW
Indoor Unit CompatibilityWide range
Maximum Piping LengthUp to 1000 m
Power Supply380-415V, 50Hz, 3-phase
Maximum Height DifferenceUp to 50 meters

Related product manuals