18 | Piping installation
Installer and user reference guide
71
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.
Only use phosphoric acid deoxidised seamless copper.
Foreign materials inside pipes (including oils for fabrication) must be
≤30mg/10m.
Temper grade: use piping with temper grade in function of the pipe diameter as
listed in table below.
Pipe Ø Temper grade of piping material
≤15.9mm O (annealed)
≥19.1mm 1/2H (half hard)
All piping lengths and distances have been taken into consideration (see "About
the piping length"[475]).
18.1.2 Refrigerant piping insulation
Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness
Ambient temperature Humidity Minimum thickness
≤30°C 75% to 80% RH 15mm
>30°C ≥80% RH 20mm
18.1.3 To select the piping size
Determine the proper size using the following tables and reference figure (only for
indication).
C
A
B
D E
C C
E
a
b
x
y
43
1 2
1,2 VRVDX indoor unit
3 Branch selector unit (BS*)
4 Cooling-only VRV indoor unit
A~E Piping
a,b Indoor branch kit
x,y Outdoor multi connection kit

Table of Contents