17 | Unit installation
Installer and user reference guide
68
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
e Moisture and dirt could enter
NOT allowed
Allowed
17.3 Mounting the outdoor unit
17.3.1 To provide the installation structure
Make sure the unit is installed level on a sufficiently strong base to prevent
vibration and noise.
NOTICE
When the installation height of the unit needs to be increased, do NOT use stands
to only support the corners.
Stands under the unit must be at least 100mm wide.
≥100 mm
≥100 mm
*
NOT allowed
Allowed (* = preferred installation)
The height of the foundation must at least be 150mm from the floor. In heavy
snowfall areas, this height should be increased, depending on the installation
place and condition.
The preferred installation is on a solid longitudinal foundation (steel beam frame
or concrete). The foundation must be larger than the grey marked area.
729
≤613
≥929
AB
AA
a
(mm)
Minimum foundation
a Anchor point (4×)
HP AA AB
5~12 766 992
14~20 1076 1302
Fasten the unit in place using four foundation bolts M12. It is best to screw in the
foundation bolts until their length remains 20mm above the foundation surface.
20 mm

Table of Contents

Other manuals for Daikin VRV IV+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV+ and is the answer not in the manual?

Daikin VRV IV+ Specifications

General IconGeneral
BrandDaikin
ModelVRV IV+
CategoryHeat Pump
LanguageEnglish

Related product manuals