23 | Maintenance and service
Installer and user reference guide
153
REYQ8~20+REMQ5U7Y1B
VRV IV+ heat recovery
4P561154-1A – 2020.10
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
NOTICE
Make sure to NOT recover any oil while recovering refrigerant. Example: By using an
oil separator.

Table of Contents

Other manuals for Daikin VRV IV+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV+ and is the answer not in the manual?

Daikin VRV IV+ Specifications

General IconGeneral
TypeVRV (Variable Refrigerant Volume)
SeriesVRV IV+
RefrigerantR-410A
Energy EfficiencyHigh
Inverter TechnologyYes
Operating Temperature Range (Cooling)-5°C to 46°C
Cooling Capacity Range22.4 kW - 168 kW
Indoor Unit CompatibilityWide range
Maximum Piping LengthUp to 1000 m
Power Supply380-415V, 50Hz, 3-phase
Maximum Height DifferenceUp to 50 meters

Related product manuals