Table 6: Definition of Data Values
Data request
number
Description Bits Details
0 Reserved
1 Production information 0–7 Reserved
8–15 Product type code:
15=MCD 600
2 Starter state 0–3 1=Ready
2=Starting
3=Running
4=Stopping (including braking)
5=Not ready (restart delay, restart temperature check, run simulation, reset
input open)
6=Tripped
7=Programming mode
8=Jog forward
9=Jog reverse
4 0=Negative phase sequence
1=Positive phase sequence (only valid if bit 6 = 1)
5 1=Current exceeds FLC
6 0=Uninitialized
1=Initialized
7 1=Communication error between device and soft starter
8–15 See 4.5 Trip Codes
3 Motor current 0–7 Average rms current across all phases (low byte)
8–15 Average rms current across all 3 phases (high byte)
4 Motor temperature 0–7 Motor thermal model (%)
8–15 Reserved
5 % Power factor 0–7 100% = power factor of 1
8–15 Reserved
Data Structures
Installation Guide | PROFIBUS Card
AQ277154583779en-000101 / 175R1181
10 | Danfoss A/S © 2018.09