Description Bits Details
6 Power (kW) 0–11 Power
12–15 Power scale
0=Multiply power by 10 to get W
1=Multiply power by 100 to get W
2=Power (kW)
3=Multiply power by 10 to get kW
7 Power (kVA) 0–11 Power
12–15 Power scale
0=Multiply power by 10 to get VA
1=Multiply power by 100 to get VA
2=Power (kVA)
3=Multiply power by 10 to get kVA
8 Voltage 0–13 Average rms voltage across all 3 phases
14–15 Reserved
9 Current 0–13 Phase 1 current (rms)
14–15 Reserved
10 Current 0–13 Phase 2 current (rms)
14–15 Reserved
11 Current 0–13 Phase 3 current (rms)
14–15 Reserved
12 Voltage 0–13 Phase 1 voltage
14–15 Reserved
13 Voltage 0–13 Phase 2 voltage
14–15 Reserved
14 Voltage 0–13 Phase 3 voltage
14–15 Reserved
15 Version 0–7 Software minor version number
8–15 Software major version number