PVED-CLS hydraulic configuration P3072-P3097
Navigate to the hydraulic configuration section via System Navigator > Configuration > Hydraulic
Config
Example parameter settings
If the parameter change is not described below or conditions are not met, use the default values.
Parameter settings
Parameter Conditions for value changes
P3072 Not present if there is no cut-off valve (usually with EHPS)
P3078 Set to 0 if PVED-CLS is part of desk setup
P3097 Set to 50 if using 12V coil on a 24V system
P3080 Set to "YES" if using EHPS
P3081 Set to match the valve type used
P3082 If using EHPS, enter desired turns lock-to-lock x100 that matches the hydraulic system
P3084 Set to match OSP displacement in cubic centimeters
P3086 Set to match volume needed to turn lock-to-lock. If using unbalanced cylinder, set to average of left and right.
The default parameters are based on 12V coil. Depending on the voltage, the following parameters may
need to be changed:
Parameter 12V coil 24V coil
P3074 1100mA 550mA
P3076 500mA 250mA
The pre-load parameter P3097 is a PWM signal and it must be set to scale the input voltage down to the
rated current of the spool:
Application Guide
PVED-CLS startup guide
Parameter setting
©
Danfoss | October 2018 AB285975085591en-000101 | 7