VLT
®
5000 Series
224 Warning: High current
(WARN. CURRENT HI)
Value:
Parameter 223 - I
VLT,MAX
I
VLT,MAX
Function:
f the motor current gets above the limit programmed
in this parameter, I
HIGH
, the display will indicate
CURRENT HIGH.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The upper signal limit of the motor current, I
HIGH
,must
be programmed within the normal working range of the
frequency converter. See drawing at parameter 223.
225 Warning: Low frequency
(WARN. FREQ. LOW)
Value:
0.0 - parameter 226
0.0 Hz
Function:
When the motor frequency is below the limit
programmed in this parameter, f
LOW
,thedisplay
indicates FREQUENCY LOW.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The lower signal limit of the motor frequency, f
LOW
,
is to be programmed within the normal working
range of the frequency converter.
See drawing at parameter 223.
226 Warning: High frequency
(WARN. FREQ. HIGH)
Value:
parameter 225 - parameter 202
132.0 Hz
Function:
When the motor frequency is above the limit
programmed in this parameter, f
HIGH
,thedisplay
will indicate FREQUENCY HIGH.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The upper signal limit of the motor frequency, f
HIGH
,
must be programmed within the normal working
range of the frequency converter.
See drawing at parameter 223.
227 Warning: Low feedback
(WARN. FEEDB. LOW)
Value:
-100,000.000 - parameter 228.
-4000.000
Function:
If the connected feedback signal gets below the
value set in this parameter, the signal outputs can
be programmed to transmit a status signal via
terminal 42 or 45 and via relay output 01 or 04
(parameter 319, 321, 323 or 326).
Description of choice:
Set the desired value.
228 Warning: High feedback
(WARN. FEEDB HIGH)
Value:
parameter 227 - 100,000.000
4000.000
Function:
If the connected feedback signal gets above the
value set in this parameter, the signal outputs can
be programmed to transmit a status signal via
terminal 42 or 45 and via relay output 01 or 04
(parameter 319, 321, 323 or 326).
Description of choice:
Set the desired value.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
120

Table of Contents

Other manuals for Danfoss VLT 5000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 5000 Series and is the answer not in the manual?

Danfoss VLT 5000 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 5000 Series
CategoryDC Drives
LanguageEnglish

Related product manuals