VLT
®
5000 Series
224 Warning: High current
(WARN. CURRENT HI)
Value:
Parameter 223 - I
VLT,MAX
✭ I
VLT,MAX
Function:
f the motor current gets above the limit programmed
in this parameter, I
HIGH
, the display will indicate
CURRENT HIGH.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The upper signal limit of the motor current, I
HIGH
,must
be programmed within the normal working range of the
frequency converter. See drawing at parameter 223.
225 Warning: Low frequency
(WARN. FREQ. LOW)
Value:
0.0 - parameter 226
✭ 0.0 Hz
Function:
When the motor frequency is below the limit
programmed in this parameter, f
LOW
,thedisplay
indicates FREQUENCY LOW.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The lower signal limit of the motor frequency, f
LOW
,
is to be programmed within the normal working
range of the frequency converter.
See drawing at parameter 223.
226 Warning: High frequency
(WARN. FREQ. HIGH)
Value:
parameter 225 - parameter 202
✭ 132.0 Hz
Function:
When the motor frequency is above the limit
programmed in this parameter, f
HIGH
,thedisplay
will indicate FREQUENCY HIGH.
The signal outputs can be programmed to transmit a
status signal via terminal 42 or 45 and via relay output
01 or 04 (parameter 319, 321, 323 or 326).
Description of choice:
The upper signal limit of the motor frequency, f
HIGH
,
must be programmed within the normal working
range of the frequency converter.
See drawing at parameter 223.
227 Warning: Low feedback
(WARN. FEEDB. LOW)
Value:
-100,000.000 - parameter 228.
✭ -4000.000
Function:
If the connected feedback signal gets below the
value set in this parameter, the signal outputs can
be programmed to transmit a status signal via
terminal 42 or 45 and via relay output 01 or 04
(parameter 319, 321, 323 or 326).
Description of choice:
Set the desired value.
228 Warning: High feedback
(WARN. FEEDB HIGH)
Value:
parameter 227 - 100,000.000
✭ 4000.000
Function:
If the connected feedback signal gets above the
value set in this parameter, the signal outputs can
be programmed to transmit a status signal via
terminal 42 or 45 and via relay output 01 or 04
(parameter 319, 321, 323 or 326).
Description of choice:
Set the desired value.
✭ = factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
120