VLT
®
8000 AQUA
Technical data, mains supply 3 x 380 - 480 V
According to international requirements VLT type 8006 8008 8011
Output current I
VLT,N
[A] (380-440 V) 10.0 13.0 16.0
I
VLT, MAX
(60 s) [A]
(380-440 V)
11.0 14.3 17.6
I
VLT, N
[A] (441-480 V) 8.2 11.0 14.0
I
VLT, MAX
(60 s) [A]
(441-480 V)
9.0 12.1 15.4
Output power S
VLT,N
[kVA] (400 V) 7.2 9.3 11.5
S
VLT,N
[kVA] (460 V) 6.5 8.8 11.2
Typical shaft output P
VLT,N
[kW] 4.0 5.5 7.5
Typical shaft output P
VLT,N
[HP] 5 7.5 10
Max. cable cross-section
to motor
[mm
2
]/[AWG]
2) 4)
4/10 4/10 4/10
Max. input current I
L,N
[A] (380 V) 9.1 12.2 15.0
(RMS) I
L,N
[A] (480 V) 8.3 10.6 14.0
Max. cable
cross-section power
[mm
2
]/[AWG]
2) 4)
4/10 4/10 4/10
Max. pre-fuses [-]/UL
1)
[A] 25/20 25/25 35/30
Efficiency
3)
0.96 0.96 0.96
Weight IP 20/NEMA 1 [kg/lbs] 10.5/23 10.5/23 10.5/23
Weight IP 54/NEMA 12 [kg/lbs] 14/31 14/31 14/31
Power loss at
max. load. [W]
Total 198 250 295
Enclosure VLT type IP 20/NEMA 1/IP 54/NEMA 12
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m/100 ft screened motor cables at rated load and rated frequency.
4. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
MG.83.A2.02 - VLT is a registered Danfoss trademark
38