3.11 Parameters: Profibus
3.11.1 9-** Profibus
Parameter group for all Profibus-specific parameters.
9-00 Setpoint
Range: Function:
0* [0 - 65535 ] This parameter receives cyclical reference from a Master Class 2. If the control priority is set to
Master Class 2, the reference for the frequency converter is taken from this parameter, whereas the
cyclical reference will be ignored.
9-07 Actual Value
Range: Function:
0* [0 - 65535 ] This parameter delivers the MAV for a Master Class 2. The parameter is valid if the control priority
is set to Master Class 2.
9-15 PCD Write Configuration
Array [10]
Option: Function:
Select the parameters to be assigned to PCD 3 to 10 of the telegrams. The number of available
PCDs depends on the telegram type. The values in PCD 3 to 10 will then be written to the selected
parameters as data values. Alternatively, specify a standard Profibus telegram in par. 9-22
Telegram
Selection
.
[0] * None
[302] Minimum Reference
[303] Maximum Reference
[312] Catch up/slow Down Value
[341] Ramp 1 Ramp up Time
[342] Ramp 1 Ramp Down Time
[351] Ramp 2 Ramp up Time
[352] Ramp 2 Ramp down Time
[380] Jog Ramp Time
[381] Quick Stop Ramp Time
[411] Motor Speed Low Limit [RPM]
[412] Motor Speed Low Limit [Hz]
[413] Motor Speed High Limit [RPM]
[414] Motor Speed High Limit [Hz]
[416] Torque Limit Motor Mode
[417] Torque Limit Generator Mode
[590] Digital & Relay Bus Control
[593] Pulse Out #27 Bus Control
[595] Pulse Out #29 Bus Control
[597] Pulse Out #X30/6 Bus Control
[653] Terminal 42 Output Bus Control
[663] Terminal X30/8 Bus Control
[673] Terminal X45/1 Bus Control
[683] Terminal X45/3 Bus Control
[890] Bus Jog 1 Speed
3 Parameter descriptions FC 300 Programming Guide
150
MG.33.M8.02 - VLT
®