2.1.7 Quick Menu Key Functions
Pressing [Quick Menus] The list indicates the different areas contained in
the Quick menu.
Select
My Personal Menu
to display the chosen personal parameters.
These parameters are selected in par. 0-25
My Personal Menu
. Up to 20
different parameters can be added in this menu.
Select
Quick setup
to go through a limited amount of parameters to get the motor running almost optimally. The default setting for the other parameters
considers the desired control functions and the configuration of signal inputs/outputs (control terminals).
The selection of parameter is effected by means of the arrow keys. The parameters in the following table are accessible.
Parameter Setting
Par. 0-01
Language
Par. 1-20
Motor Power [kW]
[kW]
Par. 1-22
Motor Voltage
[V]
Par. 1-23
Motor Frequency
[Hz]
Par. 1-24
Motor Current
[A]
Par. 1-25
Motor Nominal Speed
[rpm]
Par. 5-12
Terminal 27 Digital Input
[0] No function*
Par. 1-29
Automatic Motor Adaptation (AMA)
[1] Enable complete AMA
Par. 3-02
Minimum Reference
[rpm]
Par. 3-03
Maximum Reference
[rpm]
Par. 3-41
Ramp 1 Ramp up Time
[sec]
Par. 3-42
Ramp 1 Ramp Down Time
[sec]
Par. 3-13
Reference Site
* If terminal 27 is set to “no function”, no connection to +24 V on terminal 27 is necessary.
Select
Changes made
to get information about:
•
the last 10 changes. Use the [
▲
] [
▼
] navigation keys to scroll between the last 10 changed parameters.
• the changes made since default setting.
Select
Loggings
to get information about the display line read-outs. The information is shown as graphs.
Only display parameters selected in par. 0-20
Display Line 1.1 Small
and par. 0-24
Display Line 3 Large
can be viewed. It is possible to store up to 120
samples in the memory for later reference.
FC 300 Programming Guide 2 How to Programme
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
21