2.1.8 Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using LCP 102 (read
table from left to right). The example applies to open loop applications:
Press
Q2 Quick Menu
Par. 0-01
Language
Set language
Par. 1-20
Motor Power [kW]
Set Motor nameplate power
Par. 1-22
Motor Voltage
Set Nameplate voltage
Par. 1-23
Motor Frequency
Set Nameplate frequency
Par. 1-24
Motor Current
Set Nameplate current
Par. 1-25
Motor Nominal Speed
Set Nameplate speed in RPM
Par. 5-12
Terminal 27 Digital Input
If terminal default is
Coast inverse
it is possible to change this
setting to
No function
. No connection to terminal 27 is then
needed for running AMA
Par. 1-29
Automatic Motor Adaptation
(AMA)
Set desired AMA function. Enable complete AMA is recommen-
ded
Par. 3-02
Minimum Reference
Set the minimum speed of the motor shaft
Par. 3-03
Maximum Reference
Set the maximum speed of the motor shaft
Par. 3-41
Ramp 1 Ramp up Time
Set the ramping up time with reference to synchronous motor
speed, n
s
Par. 3-42
Ramp 1 Ramp Down Time
Set the ramping downdecel time with reference to synchronous
motor speed, n
s
Par. 3-13
Reference Site
Set the site from where the reference must work
2 How to Programme FC 300 Programming Guide
22
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
2