[5] Torque limit
Torque limit
[5] The torque limit, set in par. 4-16
Torque Limit Motor Mode
or par. 4-17
Torque
Limit Generator Mode
, has been exceeded.
[6] Current limit
Current limit
[6] The motor current limit, set in par. 4-18
Current Limit
, has been exceeded.
[7] Out of current range
Out of current range
[7] The motor current is outside the range set in par. 4-18
Current Limit
.
[8] Below I low
Below I low
[8] The motor current is lower than set in par. 4-50
Warning Current Low
.
[9] Above I high
Above I high
[9] The motor current is higher than set in par. 4-51
Warning Current High
.
[10] Out of speed range
Out of speed range
[10] The speed is outside the range set in par. 4-52
Warning Speed Low
and
par. 4-53
Warning Speed High
.
[11] Below speed low
Below speed low
[11] The output speed is lower than the setting in par. 4-52
Warning Speed Low
.
[12] Above speed high
Above speed high
[12] The output speed is higher than the setting in par. 4-53
Warning Speed
High
.
[13] Out of feedb. range
Out of feedb. Range
[13] The feedback is outside the range set in par. 4-56
Warning Feedback
Low
and par. 4-57
Warning Feedback High
.
[14] Below feedb. low
Below feedb. Low
[14] The feedback is below the limit set in par. 4-56
Warning Feedback Low
.
[15] Above feedb. high
Above feedb. High
[15] The feedback is above the limit set in par. 4-57
Warning Feedback High
.
[16] Thermal warning
Thermal warning
[16] The thermal warning turns on when the temperature exceeds the limit in the
motor, the frequency converter, the brake resistor or the thermistor.
[17] Mains out of range
Mains out of range
[17] The mains voltage is outside the specified voltage range.
[18] Reversing
Reversing
[18] The output is high when the frequency converter is running counter clockwise (the
logical product of the status bits “running” AND “reverse”).
[19] Warning
Warning
[19] A warning is active.
[20] Alarm (trip)
Alarm (trip)
[20] A (trip) alarm is active.
[21] Alarm (trip lock)
Alarm (trip lock)
[21] A (Trip lock) alarm is active.
[22] Comparator 0
Comparator 0
[22] Use the result of comparator 0.
[23] Comparator 1
Comparator 1
[23] Use the result of comparator 1.
[24] Comparator 2
Comparator 2
[24] Use the result of comparator 2.
[25] Comparator 3
Comparator 3
[25] Use the result of comparator 3.
[26] Logic rule 0
Logic rule 0
[26] Use the result of logic rule 0.
[27] Logic rule 1
Logic rule 1
[27] Use the result of logic rule 1.
[28] Logic rule 2
Logic rule 2
[28] Use the result of logic rule 2.
[29] Logic rule 3
Logic rule 3
[29] Use the result of logic rule 3.
[33] Digital input DI18
Digital input DI18
[33] Use the result of digital input 18.
[34] Digital input DI19
Digital input DI19
[34] Use the result of digital input 19.
[35] Digital input DI27
Digital input DI27
[35] Use the result of digital input 27.
[36] Digital input DI29
Digital input DI27
[35] Use the result of digital input 29.
[37] Digital input DI32
Digital input DI32
[37] Use the result of digital input 32.
[38] Digital input DI33
Digital input DI33
[38] Use the result of digital input 33.
[39] Start command
Start command
[39] A start command is issued.
[40] Drive stopped
Drive stopped
[40] A stop command ( Jog, Stop, Qstop, Coast) is issued – and not from the SLC
itself.
FC 300 Programming Guide 3 Parameter descriptions
MG.33.M8.02 - VLT
®
is a registered Danfoss trademark
177
3