5.3 System Set-up
Procedure
Perform automatic motor adaption (AMA):
Set the basic motor parameters before performing AMA.
Table 6: Basic Parameters to be Checked before AMA
Parameter 1-10 Motor Construction
ASM
SPM
IPM
SynRM
PMaSynRM
Parameter 1-20 Motor Power [kW]/parameter 1-21 Motor Power
[hp]
X
Parameter 1-22 Motor Voltage
X
Parameter 1-23 Motor Frequency
X
X
X
Parameter 1-24 Motor Current
X
X
X
X
X
Parameter 1-25 Motor Nominal Speed
X
X
X
X
X
Parameter 1-26 Motor Cont. Rated
X
X
X
X
Parameter 1-39 Motor Poles
X
X
X
X
Optimize the compatibility between motor and drive via parameter 1-29 Automatic Motor Adaptation (AMA).
Check motor rotatation.
If encoder feedback is used, perform the following steps:
Select [0] Speed open loop in parameter 1-00 Configuration Mode.
Select [1] 24V encoder in parameter 7-00 Speed PID Feedback Source.
Press [Hand On].
Press [] for positive speed reference (parameter 1-06 Clockwise Direction at [0]).
In parameter 16-57 Feedback [RPM], check that the feedback is positive.
AQ267037727118en-000101 / 130R030024 | Danfoss A/S © 2021.01
Commissioning
VLT® AutomationDrive FC 301/FC 302
Operating Guide

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 301

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 301 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 301 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 301
CategoryDC Drives
LanguageEnglish

Related product manuals