Parameter 6-71 Terminal 45 Analog Output [100] Output
frequency
Parameter 6-90 Terminal 42 Mode [0] 0–20 mA
Parameter 6-91 Terminal 42 Analog Output [103] Motor Current
Parameter 7-20 Process CL Feedback 1
Resource
[2] Analog input 54
Table 6.1 Process Closed Loop
Application
Local/remote.
Parameter 0-16 Application Selection is set to [2] Local/Remote.
Description
For applications where the speed reference can be switched
between local potentiometer and remote current signal.
+24V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 3
2DI6 3
3DI7 3
1
COM 20
+10V 50
AI1
53
-
+
AI2
54
COM 55
AO1
4
5AO2 4
2
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Setup select
4-20
mA
130BC431.11
Parameter settings Set-up 1 Set-up 2
Parameter 0-10 Active Set-
up
[9] Multi Set-up [9] Multi Set-up
Parameter 0-12 Link Setups [20] Linked [20] Linked
Parameter 1-00 Congu-
ration Mode
[0] Speed Open Loop [0] Speed Open
Loop
Parameter 3-00 Reference
Range
[0] Min–Max [0] Min–Max
Parameter 3-15 Reference 1
Source
[1] AI 53 [2] AI 54
Parameter 3-16 Reference 2
Source
[0] No function [0] No function
Parameter 4-12 Motor
Speed Low Limit [Hz]
25.0 Hz 25.0 Hz
Parameter 4-14 Motor
Speed High Limit [Hz]
50.0 Hz 50.0 Hz
Parameter 5-10 Terminal 18
Digital Input
[8] Start [8] Start
Parameter 5-12 Terminal 27
Digital Input
[2] Coast Inverse [2] Coast
Inverse
Parameter 5-14 Terminal 32
Digital Input
[23] Set-up select [23] Set-up
select
Parameter 5-40 Function
Relay (Relay 1 Selection)
[5] Running [5] Running
Parameter 5-40 Function
Relay (Relay 2 Selection)
[9] Alarm [9] Alarm
Parameter 6-10 Terminal 53
Low Voltage
0.07 V
Parameter 6-11 Terminal 53
High Voltage
10 V
Parameter 6-19 Terminal 53
mode
[1] Voltage Mode
Parameter 6-22 Terminal 54
Low Current
4.0 mA
Parameter 6-23 Terminal 54
High Current
20.0 mA
Parameter 6-29 Terminal 54
mode
[0] Current
Mode
Parameter 6-70 Terminal 45
Mode
[0] 0–20 mA [0] 0–20 mA
Parameter 6-71 Terminal 45
Analog Output
[100] Output
frequency
[100] Output
frequency
Parameter 6-90 Terminal 42
Mode
[0] 0–20 mA [0] 0–20 mA
Parameter 6-91 Terminal 42
Analog Output
[103] Motor Current [103] Motor
Current
Table 6.2 Local/Remote
Applications
VLT
®
AutomationDrive FC 360
38 Danfoss A/S © 03/2017 All rights reserved. MG06A702
6
6