Parameter 6-71 Terminal 45 Analog Output [100] Output
frequency
Parameter 6-90 Terminal 42 Mode [0] 0–20 mA
Parameter 6-91 Terminal 42 Analog Output [103] Motor Current
Parameter 7-20 Process CL Feedback 1
Resource
[2] Analog input 54
Table 6.1 Process Closed Loop
Application
Local/remote.
Parameter 0-16 Application Selection is set to [2] Local/Remote.
Description
For applications where the speed reference can be switched
between local potentiometer and remote current signal.
+24V 12
DI1 18
DI2 19
DI3 27
DI4 29
DI5 3
2DI6 3
3DI7 3
1
COM 20
+10V 50
AI1
53
-
+
AI2
54
COM 55
AO1
4
5AO2 4
2
1
2
3
4
5
6
R1
R2
FC 360
Start
Coast inverse
Setup select
4-20
mA
130BC431.11
Parameter settings Set-up 1 Set-up 2
Parameter 0-10 Active Set-
up
[9] Multi Set-up [9] Multi Set-up
Parameter 0-12 Link Setups [20] Linked [20] Linked
Parameter 1-00 Congu-
ration Mode
[0] Speed Open Loop [0] Speed Open
Loop
Parameter 3-00 Reference
Range
[0] Min–Max [0] Min–Max
Parameter 3-15 Reference 1
Source
[1] AI 53 [2] AI 54
Parameter 3-16 Reference 2
Source
[0] No function [0] No function
Parameter 4-12 Motor
Speed Low Limit [Hz]
25.0 Hz 25.0 Hz
Parameter 4-14 Motor
Speed High Limit [Hz]
50.0 Hz 50.0 Hz
Parameter 5-10 Terminal 18
Digital Input
[8] Start [8] Start
Parameter 5-12 Terminal 27
Digital Input
[2] Coast Inverse [2] Coast
Inverse
Parameter 5-14 Terminal 32
Digital Input
[23] Set-up select [23] Set-up
select
Parameter 5-40 Function
Relay (Relay 1 Selection)
[5] Running [5] Running
Parameter 5-40 Function
Relay (Relay 2 Selection)
[9] Alarm [9] Alarm
Parameter 6-10 Terminal 53
Low Voltage
0.07 V
Parameter 6-11 Terminal 53
High Voltage
10 V
Parameter 6-19 Terminal 53
mode
[1] Voltage Mode
Parameter 6-22 Terminal 54
Low Current
4.0 mA
Parameter 6-23 Terminal 54
High Current
20.0 mA
Parameter 6-29 Terminal 54
mode
[0] Current
Mode
Parameter 6-70 Terminal 45
Mode
[0] 0–20 mA [0] 0–20 mA
Parameter 6-71 Terminal 45
Analog Output
[100] Output
frequency
[100] Output
frequency
Parameter 6-90 Terminal 42
Mode
[0] 0–20 mA [0] 0–20 mA
Parameter 6-91 Terminal 42
Analog Output
[103] Motor Current [103] Motor
Current
Table 6.2 Local/Remote
Applications
VLT
®
AutomationDrive FC 360
38 Danfoss A/S © 03/2017 All rights reserved. MG06A702
6
6

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals