8.2 General Technical Data
Mains supply (L1, L2, L3)
Supply terminals L1, L2, L3
Supply voltage 380–480 V: -15% (-25%)
1)
to +10%
1) The frequency converter can run at -25% input voltage with reduced performance. The maximum output power of the
frequency converter is 75% if input voltage is -25%, and 85% if input voltage is -15%.
Full torque cannot be expected at mains voltage lower than 10% below the lowest rated supply voltage of the frequency
converter.
Supply frequency 50/60 Hz ±5%
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage
True power factor (λ) 0.9 nominal at rated load
Displacement power factor (cos ϕ) Near unity (>0.98)
Switching on input supply L1, L2, L3 (power-ups) 7.5 kW Maximum 2 times/minute
Switching on input supply L1, L2, L3 (power-ups) 11–75 kW Maximum 1 time/minute
Motor output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency in U/f mode (for AM motor) 0–500 Hz
Output frequency in VVC
+
mode (for AM motor) 0–200 Hz
Output frequency in VVC
+
mode (for PM motor) 0–400 Hz
Switching on output Unlimited
Ramp time 0.01–3600 s
Torque characteristics
Starting torque (high overload)
Maximum 160% for 60 s
1)
Overload torque (high overload) Maximum 160% for 60 s
1)
Starting torque (normal overload) Maximum 110% for 60 s
1)
Overload torque (normal overload) Maximum 110% for 60 s
Starting current Maximum 200% for 1 s
Torque rise time in VVC
+
(independent of f
sw
) Maximum 50 ms
1) Percentage relates to the nominal torque. It is 150% for 11–75 kW (15–100 hp) frequency converters.
Cable lengths and cross-sections
1)
Maximum motor cable length, shielded 50 m (164 ft)
Maximum motor cable length, unshielded 0.37–22 kW (0.5–30 hp): 75 m (246 ft), 30–75 kW (40–100 hp): 100 m (328 ft)
Maximum cross-section to control terminals, exible/rigid wire 2.5 mm
2
/14 AWG
Minimum cross-section to control terminals 0.55 mm
2
/30 AWG
1) For power cables, see Table 8.1 to Table 8.3.
Digital inputs
Programmable digital inputs 7
Terminal number 18, 19, 27
1)
, 29
1)
, 32, 33, 31
Logic PNP or NPN
Voltage level 0–24 V DC
Voltage level, logic 0 PNP < 5 V DC
Voltage level, logic 1 PNP > 10 V DC
Voltage level, logic 0 NPN > 19 V DC
Voltage level, logic 1 NPN < 14 V DC
Maximum voltage on input 28 V DC
Pulse frequency range 4 Hz–32 kHz
(Duty cycle) minimum pulse width 4.5 ms
Input resistance, R
i
approximately 4 kΩ
1) Terminals 27 and 29 can also be programmed as output.
Specications
VLT
®
AutomationDrive FC 360
56 Danfoss A/S © 03/2017 All rights reserved. MG06A702
88

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals