Ambient conditions
Enclosure sizes J1–J7 IP20
Vibration test, all enclosure sizes 1.0 g
Relative humidity 5–95% (IEC 721-3-3); Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test Class Kd
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating Maximum 55 °C (131 °F)
1)
- at full continuous output current with some power size Maximum 50 °C (122 °F)
- at full continuous output current Maximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)
Minimum ambient temperature at reduced performance -10 °C (14 °F)
Temperature during storage/transport -25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating 1000 m (3281 ft)
Maximum altitude above sea level with derating 3000 m (9843 ft)
EMC standards, emission
EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
EN 61000-3-12, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Energy eciency class
1)
IE2
1) Determined according to EN 50598-2 at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
Control card performance
Scan interval 1 ms
Protection and features
Electronic thermal motor protection against overload.
Temperature monitoring of the heat sink ensures that the frequency converter trips when the temperature reaches
a predened level. An overload temperature cannot be reset until the temperature of the heat sink is below the
temperature limit.
The frequency converter is protected against short circuits on motor terminals U, V, W.
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load and
parameter setting).
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips when the intermediate
circuit voltage is too low or too high.
The frequency converter is protected against ground faults on motor terminals U, V, W.
Specications Quick Guide
MG06A702 Danfoss A/S © 03/2017 All rights reserved. 59
8 8

Other manuals for Danfoss VLT AutomationDrive FC 360

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 360 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 360 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 360
CategoryDC Drives
LanguageEnglish

Related product manuals