Ambient conditions
Enclosure sizes J1–J7 IP20
Vibration test, all enclosure sizes 1.0 g
Relative humidity 5–95% (IEC 721-3-3); Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test Class Kd
Test method according to IEC 60068-2-43 H
2
S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating Maximum 55 °C (131 °F)
1)
- at full continuous output current with some power size Maximum 50 °C (122 °F)
- at full continuous output current Maximum 45 °C (113 °F)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)
Minimum ambient temperature at reduced performance -10 °C (14 °F)
Temperature during storage/transport -25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating 1000 m (3281 ft)
Maximum altitude above sea level with derating 3000 m (9843 ft)
EMC standards, emission
EN 61800-3, EN 61000-3-2, EN 61000-3-3, EN 61000-3-11,
EN 61000-3-12, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, immunity
EN 61800-3, EN 61000-6-1/2, EN 61000-4-2,
EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Energy eciency class
1)
IE2
1) Determined according to EN 50598-2 at:
•
Rated load.
•
90% rated frequency.
•
Switching frequency factory setting.
•
Switching pattern factory setting.
Control card performance
Scan interval 1 ms
Protection and features
•
Electronic thermal motor protection against overload.
•
Temperature monitoring of the heat sink ensures that the frequency converter trips when the temperature reaches
a predened level. An overload temperature cannot be reset until the temperature of the heat sink is below the
temperature limit.
•
The frequency converter is protected against short circuits on motor terminals U, V, W.
•
If a mains phase is missing, the frequency converter trips or issues a warning (depending on the load and
parameter setting).
•
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips when the intermediate
circuit voltage is too low or too high.
•
The frequency converter is protected against ground faults on motor terminals U, V, W.
Specications Quick Guide
MG06A702 Danfoss A/S © 03/2017 All rights reserved. 59