Page #45 background image
Terminal Parameter Default
setting
Description
61 Integrated RC-lter to
connect cable shield
if there are EMC
problems.
68 (+) Parameter
group 8-3* FC
Port Settings
RS485 interface. A
switch (BUS TER.) is
provided on the
control card for bus
termination
resistance.
69 (-) Parameter
group 8-3* FC
Port Settings
Table 7.2 Serial Communication Terminal Descriptions
Terminal Parameter Default
setting
Description
12, 13 +24 V DC 24 V DC supply
voltage for digital
inputs and external
transducers.
Maximum output
current 200 mA for all
24 V loads.
18 Parameter 5-10
Terminal 18
Digital Input
[8] Start Digital inputs.
19 Parameter 5-11
Terminal 19
Digital Input
[10]
Reversing
32 Parameter 5-14
Terminal 32
Digital Input
[0] No
operation
33 Parameter 5-15
Terminal 33
Digital Input
[0] No
operation
27 Parameter 5-12
Terminal 27
Digital Input
[2] Coast
inverse
For digital input or
output. Default
setting is input.
29 Parameter 5-13
Terminal 29
Digital Input
[14] JOG
20 Common for digital
inputs and 0 V
potential for 24 V
supply.
Table 7.3 Digital Input/Output Terminal Descriptions
Terminal Parameter Default
setting
Description
39 Common for analog
output.
42 Parameter 6-50
Terminal 42
Output
[0] No
operation
Programmable analog
output. 0–20 mA or
4–20 mA at a
maximum of 500 Ω.
50 +10 V DC 10 V DC analog
supply voltage for
potentiometer or
thermistor. 15 mA
maximum.
53 Parameter
group 6-1*
Analog Input 1
Reference Analog input. For
voltage or current.
Switches A53 and
A54 select mA or V.
54 Parameter
group 6-2*
Analog Input 2
Feedback
55 Common for analog
input.
Table 7.4 Analog Input/Output Terminal Descriptions
Relay terminals
RELAY 1 RELAY 2
01 02 03 04 05 06
130BF156.10
Illustration 7.8 Relay 1 and Relay 2 Terminals
Relay 1 and relay 2. Location depends on drive
conguration. See the operating guide.
Terminals on built-in optional equipment. See the
instructions provided with the equipment option.
Terminal Parameter Default
setting
Description
01, 02, 03 Parameter 5-40
Function Relay
[0]
[0] No
operation
Form C relay output.
For AC or DC voltage
and resistive or
inductive loads.
04, 05, 06 Parameter 5-40
Function Relay
[1]
[0] No
operation
Table 7.5 Relay Terminal Descriptions
Electrical Installation Con... Design Guide
MG06K102 Danfoss A/S © 03/2019 All rights reserved. 43
7 7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 Series and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361 Series
CategoryDC Drives
LanguageEnglish

Related product manuals