5.6 Connecting the AC Mains
Size the wiring according to the input current of the drive. For maximum wire sizes, see chapter 10.1 Electrical Data,
380-480 V.
Comply with local and national electrical codes for cable sizes.
Procedure
1. Strip a section of the outer cable insulation.
2. Position the stripped wire under the cable clamp, establishing mechanical xation and electrical contact between
the cable shield and ground.
3. Connect the ground wire to the nearest grounding terminal in accordance with the grounding instructions
provided in chapter 5.4 Connecting to Ground.
4. Connect the 3-phase AC input power wiring to terminals R, S, and T (see Illustration 5.5).
5. When supplied from an isolated mains source (IT mains or oating delta) or TT/TN-S mains with a grounded leg
(grounded delta), ensure that parameter 14-50 RFI Filter is set to [0] O to avoid damage to the DC link and to
reduce ground capacity currents.
6. Tighten the terminals in accordance with the information provided in chapter 10.8 Fastener Tightening Torques.
Electrical Installation Operating Guide
MG06I102 Danfoss A/S © 06/2018 All rights reserved. 25
5 5

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 361 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 361 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 361
CategoryDC Drives
LanguageEnglish

Related product manuals