3.7.1. Electrical Installation, Control Cables
3.82: Diagram showing all electrical terminals without options.
Terminal 37 is the input to be used for Safe Stop. For instructions on safe stop installation, refer to the section
Safe Stop Installation
in the adjustable frequency drive Design Guide. See also sections Safe Stop and Safe
Stop Installation.
In rare cases, very long control cables and analog signals may, depending on installation, result
in 50/60 Hz ground loops due to noise from line supply cables.
If this occurs, it may be necessary to break the shield or insert a 100 nF capacitor between shield
and chassis.
The digital and analog inputs and outputs must be connected separately to the adjustable fre-
quency drive common inputs (terminal 20, 55, 39) to prevent ground currents from both groups
from affecting other groups. For example, switching on the digital input may disturb the analog
input signal.
VLT
®
Automation Drive FC 300
Instruction Manual High Power
3. How to Install
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
67
3

Table of Contents

Other manuals for Danfoss VLT FC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 and is the answer not in the manual?

Danfoss VLT FC 100 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100
CategoryDC Drives
LanguageEnglish

Related product manuals