4.1.3. Initial Commissioning
The easiest way of carrying out the initial commissioning is by using the Quick Menu button and
follow the quick set-up procedure using LCP 102 (read table from left to right):
Press
Q2 Quick Menu
0-01 Language Set language
1-20 Motor power Set motor nameplate power
1-22 Motor voltage
Set nameplate voltage
1-23 Motor frequency Set nameplate frequency
1-24 Motor current
Set nameplate current
1-25 Motor nominal speed Set nameplate speed in RPM
5-12 Terminal 27 Digital
Input
If terminal default is
Coast inverse,
it is
possible to change this setting to
No
function
. No connection to terminal 27
is then needed for running AMA
1-29 Automatic Motor
Adaptation
Set desired AMA function. Enabling
complete AMA is recommended
3-02 Minimum reference
Set the minimum speed of the motor
shaft
3-03 Maximum Reference
Set the maximum speed of the motor
shaft
3-41 Ramp1 up time
Set the ramping-up time with reference
to the nominal motor speed (set in par.
1-25)
3-42 Ramp1 down time
Set the ramping-down time with refer-
ence to the nominal motor speed (set in
par. 1-25)
3-13 Reference site
Set the site from where the reference
must work
VLT
®
Automation Drive FC 300
Instruction Manual High Power
4. How to Program
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
77
4

Table of Contents

Other manuals for Danfoss VLT FC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 and is the answer not in the manual?

Danfoss VLT FC 100 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100
CategoryDC Drives
LanguageEnglish

Related product manuals