3-02 Minimum Reference
Range: Function:
0.000
Unit
*
[-100000.000 - par.
3-03]
The
Minimum reference
is the minimum value obtained by the
sum of all references.
Minimum reference
is only active if
Min -
Max
[0] is set in par. 3-00.
3-03 Maximum Reference
Range: Function:
1500.00
0
*
[Par. 3-02 -
100000.000]
Enter the maximum reference. The maximum reference is the
highest value obtainable by adding all references together.
The Maximum Reference unit matches:
The choice of configuration in par. 1-00
Configuration
Mode
: for
Speed closed-loop
[1], RPM; for
Torque
[2],
Nm.
The unit selected in par. 3-01
Reference/Feedback
Unit
.
3-41 Ramp 1 Ramp-up Time
Range: Function:
s
*
[0.01 - 3600.00 s] Enter the ramp-up time, i.e., the acceleration time from 0 RPM
to the rated motor speed n
M,N
(par. 1-25). Choose a ramp-up
time such that the output current does not exceed the current
limit in par. 4-18 during ramping. The value 0.00 corresponds
to 0.01 sec. in speed mode. See ramp-down time in par. 3-42.
Par
.3 41 =
t
acc
s
×n
M
,
N
(
par
.1 25
)
RPM
Δ
ref RPM
4. How to Program
VLT
®
Automation Drive FC 300
Instruction Manual High Power
82
MG.33.U1.22 - VLT
®
is a registered Danfoss trademark.
4

Table of Contents

Other manuals for Danfoss VLT FC 100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 and is the answer not in the manual?

Danfoss VLT FC 100 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100
CategoryDC Drives
LanguageEnglish

Related product manuals