6.3.7 5-** Digital In / Out
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
5-0* Digital I/O mode
5-00 Digital I/O Mode [0] PNP - Active at 24V All set-ups FALSE - Uint8
5-01 Terminal 27 Mode [0] Input All set-ups TRUE - Uint8
5-02 Terminal 29 Mode [0] Input All set-ups TRUE - Uint8
5-1* Digital Inputs
5-10 Terminal 18 Digital Input [8] Start All set-ups TRUE - Uint8
5-11 Terminal 19 Digital Input [0] No operation All set-ups TRUE - Uint8
5-12 Terminal 27 Digital Input null All set-ups TRUE - Uint8
5-13 Terminal 29 Digital Input [14] Jog All set-ups TRUE - Uint8
5-14 Terminal 32 Digital Input [0] No operation All set-ups TRUE - Uint8
5-15 Terminal 33 Digital Input [0] No operation All set-ups TRUE - Uint8
5-16 Terminal X30/2 Digital Input [0] No operation All set-ups TRUE - Uint8
5-17 Terminal X30/3 Digital Input [0] No operation All set-ups TRUE - Uint8
5-18 Terminal X30/4 Digital Input [0] No operation All set-ups TRUE - Uint8
5-3* Digital Outputs
5-30 Terminal 27 Digital Output [0] No operation All set-ups TRUE - Uint8
5-31 Terminal 29 Digital Output [0] No operation All set-ups TRUE - Uint8
5-32 Term X30/6 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint8
5-33 Term X30/7 Digi Out (MCB 101) [0] No operation All set-ups TRUE - Uint8
5-4* Relays
5-40 Function Relay null All set-ups TRUE - Uint8
5-41 On Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-42 Off Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-5* Pulse Input
5-50 Term. 29 Low Frequency 100 Hz All set-ups TRUE 0 Uint32
5-51 Term. 29 High Frequency 100 Hz All set-ups TRUE 0 Uint32
5-52 Term. 29 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
5-53 Term. 29 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
5-54 Pulse Filter Time Constant #29 100 ms All set-ups FALSE -3 Uint16
5-55 Term. 33 Low Frequency 100 Hz All set-ups TRUE 0 Uint32
5-56 Term. 33 High Frequency 100 Hz All set-ups TRUE 0 Uint32
5-57 Term. 33 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
5-58 Term. 33 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
5-59 Pulse Filter Time Constant #33 100 ms All set-ups FALSE -3 Uint16
5-6* Pulse Output
5-60 Terminal 27 Pulse Output Variable [0] No operation All set-ups TRUE - Uint8
5-62 Pulse Output Max Freq #27 5000 Hz All set-ups TRUE 0 Uint32
5-63 Terminal 29 Pulse Output Variable [0] No operation All set-ups TRUE - Uint8
5-65 Pulse Output Max Freq #29 5000 Hz All set-ups TRUE 0 Uint32
5-66 Terminal X30/6 Pulse Output Variable [0] No operation All set-ups TRUE - Uint8
5-68 Pulse Output Max Freq #X30/6 5000 Hz All set-ups TRUE 0 Uint32
5-9* Bus Controlled
5-90 Digital & Relay Bus Control 0 N/A All set-ups TRUE 0 Uint32
5-93 Pulse Out #27 Bus Control 0.00 % All set-ups TRUE -2 N2
5-94 Pulse Out #27 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
5-95 Pulse Out #29 Bus Control 0.00 % All set-ups TRUE -2 N2
5-96 Pulse Out #29 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
5-97 Pulse Out #X30/6 Bus Control 0.00 % All set-ups TRUE -2 N2
5-98 Pulse Out #X30/6 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
6 How to Programme the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Operating In-
structions
126 MG.16.A1.02 - VLT
®
is a registered Danfoss trademark
6