6.3.8 6-** Analog In / Out
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8
6-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8
6-02 Fire Mode Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8
6-1* Analog Input 53
6-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-11 Terminal 53 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-12 Terminal 53 Low Current 4.00 mA All set-ups TRUE -5 Int16
6-13 Terminal 53 High Current 20.00 mA All set-ups TRUE -5 Int16
6-14 Terminal 53 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
6-15 Terminal 53 High Ref./Feedb. Value SR All set-ups TRUE -3 Int32
6-16 Terminal 53 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-17 Terminal 53 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-2* Analog Input 54
6-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-21 Terminal 54 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-22 Terminal 54 Low Current 4.00 mA All set-ups TRUE -5 Int16
6-23 Terminal 54 High Current 20.00 mA All set-ups TRUE -5 Int16
6-24 Terminal 54 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
6-25 Terminal 54 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
6-26 Terminal 54 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-27 Terminal 54 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-3* Analog Input X30/11
6-30 Terminal X30/11 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-31 Terminal X30/11 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-34 Term. X30/11 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
6-35 Term. X30/11 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
6-36 Term. X30/11 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-37 Term. X30/11 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-4* Analog Input X30/12
6-40 Terminal X30/12 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-41 Terminal X30/12 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-44 Term. X30/12 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
6-45 Term. X30/12 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
6-46 Term. X30/12 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-47 Term. X30/12 Live Zero [1] Enabled All set-ups TRUE - Uint8
6-5* Analog Output 42
6-50 Terminal 42 Output null All set-ups TRUE - Uint8
6-51 Terminal 42 Output Min Scale 0.00 % All set-ups TRUE -2 Int16
6-52 Terminal 42 Output Max Scale 100.00 % All set-ups TRUE -2 Int16
6-53 Terminal 42 Output Bus Control 0.00 % All set-ups TRUE -2 N2
6-54 Terminal 42 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
6-6* Analog Output X30/8
6-60 Terminal X30/8 Output [0] No operation All set-ups TRUE - Uint8
6-61 Terminal X30/8 Min. Scale 0.00 % All set-ups TRUE -2 Int16
6-62 Terminal X30/8 Max. Scale 100.00 % All set-ups TRUE -2 Int16
6-63 Terminal X30/8 Output Bus Control 0.00 % All set-ups TRUE -2 N2
6-64 Terminal X30/8 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
VLT HVAC Low Harmonic Drive Operating In-
structions 6 How to Programme the Low Harmonic Drive
MG.16.A1.02 - VLT
®
is a registered Danfoss trademark 127
6

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals