6.3.18 20-** FC Closed Loop
Par.
No. #
Parameter description Default value 4-set-up Change dur-
ing operation
Conver-
sion index
Type
20-0* Feedback
20-00 Feedback 1 Source [2] Analog input 54 All set-ups TRUE - Uint8
20-01 Feedback 1 Conversion [0] Linear All set-ups FALSE - Uint8
20-02 Feedback 1 Source Unit null All set-ups TRUE - Uint8
20-03 Feedback 2 Source [0] No function All set-ups TRUE - Uint8
20-04 Feedback 2 Conversion [0] Linear All set-ups FALSE - Uint8
20-05 Feedback 2 Source Unit null All set-ups TRUE - Uint8
20-06 Feedback 3 Source [0] No function All set-ups TRUE - Uint8
20-07 Feedback 3 Conversion [0] Linear All set-ups FALSE - Uint8
20-08 Feedback 3 Source Unit null All set-ups TRUE - Uint8
20-12 Reference/Feedback Unit null All set-ups TRUE - Uint8
20-13 Minimum Reference/Feedb. 0.000 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-14 Maximum Reference/Feedb. 100.000 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-2* Feedback/Setpoint
20-20 Feedback Function [3] Minimum All set-ups TRUE - Uint8
20-21 Setpoint 1 0.000 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-22 Setpoint 2 0.000 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-23 Setpoint 3 0.000 ProcessCtrlUnit All set-ups TRUE -3 Int32
20-3* Feedb. Adv. Conv.
20-30 Refrigerant [0] R22 All set-ups TRUE - Uint8
20-31 User Defined Refrigerant A1 10.0000 N/A All set-ups TRUE -4 Uint32
20-32 User Defined Refrigerant A2 -2250.00 N/A All set-ups TRUE -2 Int32
20-33 User Defined Refrigerant A3 250.000 N/A All set-ups TRUE -3 Uint32
20-34 Duct 1 Area [m2] 0.500 m2 All set-ups TRUE -3 Uint32
20-35 Duct 1 Area [in2] 750 in2 All set-ups TRUE 0 Uint32
20-36 Duct 2 Area [m2] 0.500 m2 All set-ups TRUE -3 Uint32
20-37 Duct 2 Area [in2] 750 in2 All set-ups TRUE 0 Uint32
20-38 Air Density Factor [%] 100 % All set-ups TRUE 0 Uint32
20-6* Sensorless
20-60 Sensorless Unit null All set-ups TRUE - Uint8
20-69 Sensorless Information 0 N/A All set-ups TRUE 0
VisStr[2
5]
20-7* PID Autotuning
20-70 Closed Loop Type [0] Auto 2 set-ups TRUE - Uint8
20-71 PID Performance [0] Normal 2 set-ups TRUE - Uint8
20-72 PID Output Change 0.10 N/A 2 set-ups TRUE -2 Uint16
20-73 Minimum Feedback Level -999999.000 ProcessCtrlUnit 2 set-ups TRUE -3 Int32
20-74 Maximum Feedback Level 999999.000 ProcessCtrlUnit 2 set-ups TRUE -3 Int32
20-79 PID Autotuning [0] Disabled All set-ups TRUE - Uint8
20-8* PID Basic Settings
20-81 PID Normal/ Inverse Control [0] Normal All set-ups TRUE - Uint8
20-82 PID Start Speed [RPM] SR All set-ups TRUE 67 Uint16
20-83 PID Start Speed [Hz] SR All set-ups TRUE -1 Uint16
20-84 On Reference Bandwidth 5 % All set-ups TRUE 0 Uint8
20-9* PID Controller
20-91 PID Anti Windup [1] On All set-ups TRUE - Uint8
20-93 PID Proportional Gain 0.50 N/A All set-ups TRUE -2 Uint16
20-94 PID Integral Time 20.00 s All set-ups TRUE -2 Uint32
20-95 PID Differentiation Time 0.00 s All set-ups TRUE -2 Uint16
20-96 PID Diff. Gain Limit 5.0 N/A All set-ups TRUE -1 Uint16
6 How to Programme the Low Harmonic Drive
VLT HVAC Low Harmonic Drive Operating In-
structions
138 MG.16.A1.02 - VLT
®
is a registered Danfoss trademark
6

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals