7.5 Examples
7.5.1 Writing a Parameter Value
Change par. 4-14
Motor Speed High Limit [Hz]
to 100 Hz.
Write the data in EEPROM.
PKE = E19E Hex - Write single word in par. 4-14
Motor Speed High Limit
[Hz]
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to 100 Hz, see
Conversion.
The telegram will look like this:
Note: Par. 4-14
Motor Speed High Limit [Hz]
is a single word, and the
parameter command for write in EEPROM is “E”. Parameter number 4-14
is 19E in hexadecimal.
The response from the slave to the master will be:
7.5.2 Reading a Parameter Value
Read the value in par. 3-41
Ramp 1 Ramp Up Time
PKE = 1155 Hex - Read parameter value in par. 3-41
Ramp 1 Ramp Up
Time
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. 3-41
Ramp 1 Ramp Up Time
is 10 s, the response from
the slave to the master will be:
3E8 Hex corresponds to 1000 decimal. The conversion index for par. 3-41
Ramp 1 Ramp Up Time
is -2, i.e. 0.01.
par. 3-41
Ramp 1 Ramp Up Time
is of the type
Unsigned 32
.
7 RS-485 Installation and Set-up
VLT HVAC Low Harmonic Drive Operating In-
structions
158 MG.16.A1.02 - VLT
®
is a registered Danfoss trademark
7

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals