Text block:
The text block is used to read or write texts via the data block.
7.4.7 The PKE Field
The PKE field contains two sub-fields: Parameter command and response AK, and Parameter number PNU:
Bits no. 12-15 transfer parameter commands from master to slave and return processed slave responses to the master.
Parameter commands master slave
Bit no. Parameter command
15 14 13 12
0 0 0 0 No command
0 0 0 1 Read parameter value
0 0 1 0 Write parameter value in RAM (word)
0 0 1 1 Write parameter value in RAM (double word)
1 1 0 1 Write parameter value in RAM and EEprom (double word)
1 1 1 0 Write parameter value in RAM and EEprom (word)
1 1 1 1 Read/write text
Response slave master
Bit no. Response
15 14 13 12
0 0 0 0 No response
0 0 0 1 Parameter value transferred (word)
0 0 1 0 Parameter value transferred (double word)
0 1 1 1 Command cannot be performed
1 1 1 1 text transferred
VLT HVAC Low Harmonic Drive Operating In-
structions 7 RS-485 Installation and Set-up
MG.16.A1.02 - VLT
®
is a registered Danfoss trademark 155
7

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals