Mains Supply 3 x 380 - 480 VAC
P160 P200 P250
Typical Shaft output at 400 V
[kW]
160 200 250
Typical Shaft output at 460 V
[HP]
250 300 350
Enclosure IP21 D11 D11 D11
Enclosure IP54 D11 D11 D11
Output current
Continuous
(at 400 V) [A]
315 395 480
Intermittent (60 sec overload)
(at 400 V) [A]
347 435 528
Continuous
(at 460/ 480 V) [A]
302 361 443
Intermittent (60 sec overload)
(at 460/ 480 V) [A]
332 397 487
Continuous KVA
(at 400 V) [KVA]
218 274 333
Continuous KVA
(at 460 V) [KVA]
241 288 353
Max. input current
Continuous
(at 400 V ) [A]
304 381 463
Continuous
(at 460/ 480 V) [A]
291 348 427
Max. cable size, mains motor,
brake and load share [mm
2
(AWG
2)
)]
2 x 185
(2 x 300 mcm)
2 x 185
(2 x 300 mcm)
2 x 185
(2 x 300 mcm)
Max. external pre-fuses [A]
1
400 500 630
Estimated motor power loss
at rated max. load [W]
4)
, 400 V
4029 5130 5621
Estimated motor power loss
at rated max. load [W]
4)
, 460 V
3892 4646 5126
Estimated filter losses, 400 V 4954 5714 6234
Estimated filter losses, 460 V 5279 5819 6681
Weight,
enclosure IP21, IP 54 [kg]
380 380 406
Efficiency
4)
0.96
Output frequency 0-800 Hz
Heatsink overtemp. trip
110°C 110 °C 110°C
Power card ambient trip
60 °C
VLT HVAC Low Harmonic Drive Operating In-
structions 8 General Specifications
MG.16.A1.02 - VLT
®
is a registered Danfoss trademark 165