Mains Supply 3 x 380 - 480 VAC
P500 P560 P630 P710
Typical Shaft output at 400
V [kW]
500 560 630 710
Typical Shaft output at 460
V [HP]
650 750 900 1000
Enclosure IP21, 54 F17 F17 F17 F17
Output current
Continuous
(at 400 V) [A]
880 990 1120 1260
Intermittent (60 sec over-
load)
(at 400 V) [A]
968 1089 1232 1386
Continuous
(at 460/ 480 V) [A]
780 890 1050 1160
Intermittent (60 sec over-
load)
(at 460/ 480 V) [A]
858 979 1155 1276
Continuous KVA
(at 400 V) [KVA]
610 686 776 873
Continuous KVA
(at 460 V) [KVA]
621 709 837 924
Max. input current
Continuous
(at 400 V ) [A]
857 964 1090 1227
Continuous (at 460/ 480 V)
[A]
759 867 1022 1129
Max. cable size,motor
[mm
2
(AWG
2)
)]
8x150
(8x300 mcm)
Max. cable size,mains F1/
F2 [mm
2
(AWG
2)
)]
8x240
(8x500 mcm)
Max. cable size,mains F3/
F4 [mm
2
(AWG
2)
)]
8x456
(8x900 mcm)
Max. cable size, loadshar-
ing [mm
2
(AWG
2)
)]
4x120
(4x250 mcm)
Max. cable size, brake
[mm
2
(AWG
2)
)
4x185
(4x350 mcm)
Max. external pre-fuses [A]
1
1600 2000
Est. motor power loss at
rated max. load [W]
4)
, 400
V, F1 & F2
10647 12338 13201 15436
Est. motor power loss at
rated max. load [W]
4)
,
460 V, F1 & F2
9414 11006 12353 14041
Max added losses of A1
RFI, Circuit Breaker or Dis-
connect, & Contactor, F3 &
F4
963 1054 1093 1230
Max Panel Options Losses 400
Weight,
enclosure IP21, IP 54 [kg]
2009
Weight Drive
section [kg]
1004
Weight Filter
section [kg]
1005
Efficiency
4)
0.96
Output frequency 0-600 Hz
Heatsink overtemp. trip
95 °C
Power card ambient trip
68 °C
1) For type of fuse see section
Fuses.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within +/-15% (tolerence relates to variety in voltage and cable
conditions). Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss
in the frequency converter and opposite. If the switching frequency is increased comed to the default setting, the power losses may rise sig-
nificantly.LCP and typical control card power consumptions are included. Further options and customer load may add up to 30W to the losses.
(Though typical only 4W extra for a fully loaded control card, or options for slot A or slot B, each).
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for (+/-5%).
VLT HVAC Low Harmonic Drive Operating In-
structions 8 General Specifications
MG.16.A1.02 - VLT
®
is a registered Danfoss trademark 167