VLT
®
FCD Series
Programming, FCD
300
Operation & Display
001 Language
(LANGUAGE)
Value:
English (ENGLISH)
[0]
German (DEUTSCH)
[1]
French (FRANCAIS)
[2]
Danish (DANSK)
[3]
Spanish (ESPANOL)
[4]
Italian (ITALIANO)
[5]
Function:
This parameter is used to choose the language
to be shown in the display whenever the LCP
control unit is connected.
Description of choice:
There is a choice of the languages shown.
The factory setting may vary.
002 Local/remote operation
(OPERATION SITE)
Value:
Remote operation (REMOTE)
[0]
Local operation (LOCAL)
[1]
Function:
There is a choice of two different modes of operation
of the frequency converter; Remote operation [0] or
Local operation [1]. See also parameter 013 Local
control if Local operation [1] is selected.
Description of choice:
If Remote operat ion [0] is selected, the frequency
converter is controlled via:
1. the control terminals or via serial communication.
2. the [START] key. This cannot, however, override
stop commands transmitted via the digital
inputs or via serial communication.
3. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
If Local operation [1], is selected, the frequency
converter is controlled via:
1. the [START] key. This cannot, however, override
stop commands via the digital inputs (see
parameter 013 Local control).
2. the [STOP/RESET] and [JOG] keys, on the
condition that these are active.
3. the [FWD/REV] key, on the condition that is has
been selected as active in parameter 016 Local
reversing, and that parameter 013 Local control
is set at Local control and open loop [1] or Local
control as parameter 100 [3]. Parameter 200
Output freque ncy range is set at Both directions.
4. parameter 003 Local reference where the reference
can be set using the [+] and [-] keys.
5. an external control command that can be
connected to the digital inputs (see parameter
013 Local control).
NB!:
The [JOG] and [FWD/REV] keys are located
on the LCP control unit.
003 Local reference
(LOCAL REFERENCE)
Value:
Par. 013 Local control must be set to [1] or [2]:
0-f
MAX
(par. 202)
50 Hz
Par. 013 Local control must be set to [3] or [4].
Ref
MIN
-Ref
MAX
(par. 204-205)
0,0
Function:
In this parameter, the local reference can be set
manually. The unit of the local reference depends on the
configuration selected in parameter 100 Configuration.
Description of choice:
In order to protect the local reference, parameter
002 Local/remote operation must be set to
Local operat ion [1]. Local reference cannot be
set via serial communication.
Setup configuration
There is a choice of four Setups (parameter Setups),
which can be programmed independently of one
another. The active Setup can be selected in
parameter 004 Active Setup. WhenanLCPcontrol
unit is connected, the active Setup number will be
appear in the display under "Setup". It is also possible
to preset the frequency converter to Multisetup,sothat
it is possible to shift Setups using the digital inputs
or serial communication. Setup shift can be used in
a plant in which, for example, one Setup is used for
daytime operation and another one at night time.
In parameter 006 Setup copying it is possible to copy
from one Setup to another. Using parameter 007 LCP
copy all Setups can be transferred from one frequency
converter to another by moving the LCP control panel.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
31

Table of Contents

Other manuals for Danfoss VLT FCD 303

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 303 and is the answer not in the manual?

Danfoss VLT FCD 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 303
CategoryDC Drives
LanguageEnglish

Related product manuals