■ Control word according to Fieldbus Profile
To select Profidrive in the control word, parameter 512
Telegram Profile must be set to Profidrive [0].
The control word is used to send commands
from a master (e.g. a PC) to a slave (frequency
converter). Master⇒Slave.
Bit Bit = 0 Bit =1
00 OFF 1 ON 1
01 OFF 2 ON 2
02 OFF 3 ON 3
03 Coasting stop
04 Quick stop
05 Freeze outp. freq.
06 Ramp stop Start
07 Reset
08 Bus jog 1
09 Bus jog 2
10 Data not valid Data valid
11 Slow down
12 Catch-up
13 Select Setup (lsb)
14 Select Setup (msb)
15 Reversing
Bit 00-01-02, OFF1-2-3/ON1-2-3:
Bit 00-01-02 = ’0’ causes ramp stop, which uses the
ramp time in parameters 207/208 or 209/210.
If Relay 123 is selected in parameter 323 Relay
output, the output relay will be activated when
the output frequency is 0 Hz.
Bit 00-01-02 = ’1’ means that the frequency
converter can start the motor if the other
starting conditions are fulfilled.
B
it 03, Coasting stop:
See description under Control word according
to FC protocol.
B
it 04, Quick stop:
See description under Control word according
to FC protocol.
B
it 05, Freeze output frequency:
See description under Control word according
to FC protocol.
B
it 06, Ramp stop/start:
See description under Control word according
to FC protocol.
B
it 07, Reset:
See description under Control word according
to FC protocol.
B
it 08, Jog 1:
Bit 08 = "1" means that the output frequency is
determined by parameter 09 Bus jog 1.
B
it 09, Jog 2:
Bit 09 = "1" means that the output frequency is
determined by parameter 510 Bus jog 2.
B
it 10, Data not valid/Data valid:
See description under Control word according
to FC protocol.
B
it 11, Slow-down:
Used to reduce the speed reference by the value in
parameter 219 Catch-up/slow-down reference.
Bit 11 = ’0’ does not cause any change to the reference.
Bit 11 = ’1’ means that the reference is reduced.
B
it 12, Catch-up:
Used to increase the speed reference by the value in
parameter 219 Catch-up/slow-down reference.
Bit 12 = ’0’ does not cause any change to the reference.
Bit 12 = ’1’ means that the reference is increased.
If both Slow down and Catch-up are activated (Bits
11 and 12 = "1"), slow down has the highest priority,
i.e. that the speed reference is reduced.
B
it 13/14, Selection of Setup:
See description under Control word according
to FC protocol.
B
it 15 Reversing:
See description under Control word according
to FC protocol.