VLT
®
FCD Series
207 Ramp-up time 1
(RAMP-UP TIME 1)
Value:
0.02 - 3600.00 sec
3.00 sec
Function:
The ramp-up time is the acceleration time from 0
Hz to the rated motor frequency f
M,N
(parameter
104 Motor frequency, f
M,N
). It is assumed that the
output current will not reach the current limit (set
in parameter 221 Current limit I
LIM
).
Description of choice:
Set the required ramp-up time.
208 Ramp-down time 1
(RAMPDOWNTIME1)
Value:
0.02 - 3600.00 sec
3.00 sec
Function:
The ramp-down time is the deceleration time
from the rated motor frequency f
M,N
(parameter
104 Motor frequency, f
M,N
)to0Hz,provided
no overvoltage arises in the inverter because of
generating operation of the motor.
Description of choice:
Set the required ramp-down time.
209 Ramp-up time 2
(RAMPUPTIME2)
Value:
0.02 - 3600.00 sec.
3.00 sec
Function:
See description of parameter 207 Ramp-up t ime 1.
Description of choice:
Set the required ramp-up time. Shift from ramp 1 to
ramp 2 by activating Ra mp 2 viaadigitalinput.
210 Ramp-down time 2
(RAMPDOWNTIME2)
Value:
0.02 - 3600.00 sec.
3.00 sec
Function:
See description of parameter 208 Ramp-down time 1.
Description of choice:
Set the required ramp-down time. Shift from ramp 1
to ramp 2 by activating Ramp 2 via a digital input.
211 Jog ramp time
(JOG RAMP TIME)
Value:
0.02 - 3600.00 sec.
3.00 sec
Function:
The jog ramp time is the acceleration/deceleration
time from 0 Hz to the rated motor frequency f
M,N
(parameter 104 Motor frequency, f
M,N
). It is assumed
that the output current will not reach the current
limit(setinparameter221Current limit I
LIM
).
The jog ramp time starts if a jog-signal is given via
the LCP control panel, one of the digital inputs
or the serial communication port.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
52

Table of Contents

Other manuals for Danfoss VLT FCD 303

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 303 and is the answer not in the manual?

Danfoss VLT FCD 303 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 303
CategoryDC Drives
LanguageEnglish

Related product manuals