Bit (Hex) Unit
diagnose
bit
PROFIBUS warning word
(9-53 Profibus Warning Word)
00000001 160 Connection with DP-master is not ok
00000002 161 Unused
00000004 162 FDL (Fieldbus Data link Layer) is not ok
00000008 163 Clear data command received
00000010 164 Actual value is not updated
00000020 165 Baudrate search
00000040 166 PROFIBUS ASIC is not transmitting
00000080 167 Initialising of PROFIBUS is not ok
00000100 152 Drive is tripped
00000200 153 Internal CAN error
00000400 154 Wrong configuration data from PLC
00000800 155 Wrong ID sent by PLC
00001000 156 Internal error occurred
00002000 157 Not configured
00004000 158 Timeout active
00008000 159 Warning 34 active
Table 10.18 FC 102/FC 202/FC 301/FC 302/FCD 302
Bit (Hex) Comm. option STW (16-84 Comm. Option STW)
00000001 parameterization ok
00000002 configuration ok
00000004 clearmode active
00000008 baudrate search
00000010 waiting for parameterization
00000020 waiting for configuration
00000040 in data exchange
00000080 not used
00000100 not used
00000200 not used
00000400 not used
00000800 MCL2/1 connected
00001000 MCL2/2 connected
00002000 MCL2/3 connected
00004000 data transport active
00008000 not used
Table 10.19 FC 102/FC 202/FC 301/FC 302/FCD 302
NOTICE
16-84 Comm. Option STW is not part of extended
diagnosis.
10.6 Warning and Alarm Messages
There is a clear distinction between alarms and warnings.
An alarm make the frequency converter enter a fault
condition. After the cause for the alarm has been cleared,
the master will have to acknowledge the alarm message
before the frequency converter can start operating again.
A warning condition triggers a warning which disappears
when condition returns to normal, without interfering with
the process.
Warnings
A single bit within a warning word represents warnings
within the frequency converter. Bit status [0] False means
no warning, while bit status [1] True means warning. Any
bit change in the warning word is notified by a change of
bit 7 in the status word.
Alarms
Following an alarm message, the frequency converter
enters fault condition. When the fault has been removed
and the controller has acknowledged the alarm message
by setting bit 7 in the control word, the frequency
converter resumes operation. A single bit within an alarm
word represents alarms within the frequency converter. Bit
status [0] False means no fault, while bit status [1] True
means fault.
Troubleshooting Operating Instructions
68 Danfoss A/S © Rev. 2014-02-27 All rights reserved. MG90U302
1010