WARRANTY CONDITIONS.
for Pool water applications
pH 7.2 - 7.8
Total Alkalinity 80 - 120 ppm as CaCO
3
Total Hardness 150 - 250 ppm as CaCO
3
Total dissolved solids 1000 ppm
Saline Water 8000 ppm
Chlorine - free Cl Range 1.0 - 2.0 ppm Domestic
Chlorine - free Cl Range 3.0 - 6.0 ppm Commercial
Ozone 0.9 Max ppm
Bromine 2 - 5 ppm
Baquacil 25 - 50 ppm
Aquamatic Ionic Purifier Max 2 ppm Copper
for Potable water applications
TEST RECOMMENDED LEVELS
Appearance Clear to slight haze, no debris
pH 6.6-8.5
Conductivity μS/cm More an supply mains water
Chloride ppm Less an 125
Excess Chloride ppm Less an 50
Total hardness as CaCO
3
ppm 50 to 200
Hardness deposition % Less an 30
M alkalinity as CaCO
3
ppm 300 more an supply mains
Sodium ppm 50 less an supply mains water
Potassium ppm Less an 60
Aluminium ppm Less an 3
Iron ppm Less an 50
Copper ppm Less an 3
Phosphorus ppm Less an 80
Boron ppm More an 150
Molybdenum ppm More an 20
The following exclusions apply to e Warranty given by Danerm Ltd. No
claims will be accepted if :
1. The heat pump is incorrectly sized for e application.
2. The heat pump is installed in any way at is not in accordance wi e
current procedures as defined by Danerm Ltd.
3. The heat pump has been worked upon or is adjusted by anyone oer
an a person auorised to do so by Danerm Ltd.
4. The air flow to and from e machine is outside e specified limits.
5. The water flow rough e machine is outside e specified limits.
6. The water pH level and/or chemical balance is outside e following limits:
7. The heat pump has suffered frost damage.
8. The electrical supply is insucient or in any way incorrect.
9. The fan amps and duct pressure are outside e specified limits.
10. The heat pump has not been maintained in accordance wi service
requirements in section 4.1.
If in doubt or if advice is required please contact e Danerm Group
UK Service Department by calling 01621 856 611 (option 4) or
emailing service.department@danerm.com
Note: The Reply Paid Warranty Registration Card must be returned, to ensure
at e correct warranty is given. If you do not find a Registration Card wi
your heat pump please contact e Danerm Service Department giving your
name, address and serial number of your heat pump. A card will be sent to you
for completion.
Please give MODEL NUMBER and SERIAL NUMBER of your heat pump when
making technical or service enquiries. This will assist in correct diagnosis and
ensure service can be provided wi e minimum delay.
48
SD331852 ISSUE 7
OWNER INSTALLATION MANUAL 634ACH/ACL/AHC /1222AC/1234BC/BHC /1834BHC /PP22BC